Hydraulic infrastructure plan and profile drawing for the Siriji Aductor System’s Right Branch pipeline (stations 111=0 to 188). The drawing includes both plan view and elevation profile at scales H=1:2000, V=1:200. The system consists of ductile iron pipes (K-7) in various diameters (500mm, 400mm, 300mm) with multiple derivations serving municipalities including Buenos Aires, Vicência, Aliança, Trigueiro, Caueiras, Tupaoca, and Chã de Jararaca. Several infrastructure crossings are depicted, including traversals over the Rio Siriji, under highways (BR-408, PE-074, PE-086), and over railway lines. The drawing indicates flow rates for various branches (e.g., Tupaoca at 6.21L/s) and includes pressure class specifications for pipes (PN 10, PN 16, PN 25). Technical elements include valve chambers, flow meters, and curve specifications (11°, 22°30′, 45°) at directional changes.