Transformer Detail Se1000kv DWG Detail for AutoCAD
Detail S.E. 1.000 KVA
Drawing labels, details, and other text information extracted from the CAD file (Translated from Spanish):
Lodi italy, S.r.l., In this condition: the power disconnector is in the open position. The ground disconnector is in the closed position. The door of the compact modular cell of exit will be allowing access to the interior of the cabin. The voltage indicator lamps will turn off., In this condition: the power disconnect is in the closed position with the main blades connected to the line. The ground disconnector is in the open position. The door of the compact modular cell of exit will be avoided that this will be. The voltage indicator lamps turn on., Place the lever on the axis of operation of the power disconnect switch to turn the lever towards the position for the final closing of the power disconnect the signaling will indicate closed position., With the modular cell door output the main blades of the power disconnector open with the earthing switch in position proceed to:, Set the lever on the drive shaft of the disconnector to rotate the lever in direction until the signaling indicates closed position of the earthing switch., Opening maneuver, Operation, Set the lever on the drive shaft of the disconnector to turn the lever clockwise until the signaling indicates the open position of the earthing switch., Closing maneuver, Set the lever on the axis of operation of the disconnector to turn the lever towards the position for the final opening of the power disconnector., Dry type, Kva, M.t., B.t., Dry type, B.t., M.t., electric risk, Lima Peru, Manufactured by felmec s.a., Tel .:, Manufactured by felmec s.a., fax:, Elecin, M.t., Dry type, B.t., Cell lift, T.c., Arrival cell, Transformation cell, front, Output b.t., Arrival m.t. cables, Transformation cell, Abb switch, front, Protection mesh, trunk, Capacitive insulator, Arrival cell, fan, Arrival cell, Capacitive lamp, Cell lift, Transformation cell, air extractor, Temperature control unit, HE. Modular compact, Lift cell, Transformation cell, Toroid, Capacitive insulator
Raw text data extracted from CAD file:
Language | Spanish |
Drawing Type | Detail |
Category | Water Sewage & Electricity Infrastructure |
Additional Screenshots | |
File Type | dwg |
Materials | |
Measurement Units | |
Footprint Area | |
Building Features | Car Parking Lot |
Tags | alta tensão, autocad, beleuchtung, DETAIL, détails électriques, detalhes elétrica, DWG, electrical details, elektrische details, haute tension, high tension, hochspannung, iluminação, kläranlage, kva, l'éclairage, la tour, lighting, torre, tower, transformer, treatment plant, turm |